Vijf veel voorkomende problemen van het koelsysteem
Ten eerste behandeling van onvoldoende koudemiddel
1. Storingsverschijnsel: het koeleffect van de hele machine is slecht, de waterafvoer is slechts een beetje koud en de druk aan de hoge - drukzijde en de lage - drukzijde blijkt te zijn laag zijn met de spruitstukmanometer (onder de normale snelheid van de compressor, wanneer de omgevingstemperatuur ongeveer 35 is is, de lage druk De meterindex is lager dan 1 kg / cm2, de hoge - index van de drukmeter is lager dan 10 kg / cm2), en de bellenstroom is te zien vanuit het kijkglas.
2. The cause of the failure: the refrigeration system has a refrigerant leakage point, which results in insufficient refrigerant.
3. Treatment method: 1). Use electronic leak detector to find the leak point and repair or replace parts.
2). If the parts are not replaced, only the appropriate amount of refrigerant can be added; if the parts are replaced, the appropriate amount of refrigeration oil should be added as required, and the refrigerant should be added after the system is evacuated.
Ten tweede, Overladen van koelmiddel
1. Failure phenomenon:
Het koeleffect is slecht, en de druk aan de hoge - drukzijde en de lage - drukzijde is te hoog wanneer gecontroleerd met een verdeelstukmanometer (wanneer de compressorsnelheid normaal is en de omgevingstemperatuur is 35 ° C, de hoge - manometerdruk is ongeveer 19 kg / cm2 en de lage - manometerdruk is 2,3 kg / cm2 en er zijn geen luchtbellen te zien in het kijkglas .
2. Failure reason: Too much refrigerant is added in the refrigeration system, so that the refrigeration capacity cannot be fully exerted, resulting in poor refrigeration effect.
3. Treatment method: Connect the manifold pressure gauge to the system, and slowly loosen the manual valve on the low pressure side of the manifold pressure gauge, so that the refrigerant is slowly discharged (cannot be discharged from the high pressure side, because the refrigerant will be taken out from the high pressure side) A large amount of freezing oil) until the pressure on the high and low sides is normal, and the refrigerant flows clearly from the sight glass, and occasionally bubbles flow through.
Ten derde wordt het koelsysteem gemengd met lucht
1. Storingsverschijnsel: het koelvermogen van de gehele machine wordt verminderd; de druk aan de hogedrukzijde blijkt hoog te zijn wanneer de manometer van het verdeelstuk wordt gecontroleerd en de druk aan de lagedrukzijde kan soms hoger zijn dan de normale waarde (het compressortoerental is normaal en de omgevingstemperatuur is 35 ° C Op dit moment is de druk aan de hoge - drukzijde hoger dan 20 kg / cm2; en de wijzer van de hoge - drukmeter oscilleert; aan de andere kant zijn er veel bellen te zien stromen van het kijkglas.
2. Reasons for failure:
Lucht wordt in het systeem gemengd. Vooral na montage of revisie is het vacuüm niet grondig; bij het bijvullen van het koelmiddel of het toevoegen van koelolie wordt de lucht in het systeem gebracht, of wanneer het systeem onder negatieve druk werkt, wordt de lucht door de krappe plaatsen gemengd. Nadat het koelmiddel in de lucht komt, heeft het een bepaalde druk en heeft het koelmiddel ook een bepaalde druk. In een gesloten container is de totale gasdruk gelijk aan de som van de partiële drukken, dus de metingen van de hoge en lage manometer zijn hoger dan normaal.
3. Treatment method: 1) Release refrigerant (release slowly from low pressure side with pressure gauge). 2) Check the cleanliness of the compressor oil. 3) Refill the refrigerant after vacuuming.
Fourth, & quot;ice blockage & quot; appears in the refrigeration system
1. Failure phenomenon: The refrigeration system periodically cools suddenly but not suddenly. During operation, the pointer on the low pressure side of the manifold pressure gauge often fluctuates between the negative pressure and the normal value.
2. Cause of failure: Moisture is mixed into the refrigerant in the refrigeration system. Because the water is incompatible with the refrigerant, when the refrigerant flows through the orifice of the expansion valve, the temperature drops suddenly. These are mixed in the refrigerant The water will easily form small particles of ice in the vicinity of the small hole of the throttle valve or around the valve pin hole, which is spherical or hemispherical. When the ice particles are condensed to a certain extent, the throttle channel is blocked and an ice jam fault is formed. . When ice blocking occurs due to icing, the refrigeration system cannot work properly, and the refrigeration effect is significantly reduced, even without refrigeration.
Op dit moment leek de lagedrukmeter onderdruk, dus de temperatuur van het ijsblok was duidelijk verhoogd, de ijsdeeltjes van het ijsblok smolten in water, zodat het fenomeen ijsblok verdween, het koelsysteem hervatte de normale werking, de de koeling was goed en de lagedrukzijdedruk werd weer normaal. Na een tijdje was er ijsblokkade in het systeem en werkte het systeem niet goed.
3. Treatment method: 1) Because the desiccant is in supersaturated state, it is necessary to replace the reservoir with desiccant and add 30ml of freezing oil. 2) Vacuum the system and add a specified amount of refrigerant.
Vijfde, vuile probleemoplossing voor blokkering
1. Failure phenomenon: poor cooling effect or no cooling. When the air conditioning system is running, the readings of the high and low pressure gauges on the manifold pressure gauge are less than the normal value. (When the compressor speed is normal and the ambient temperature is around 35 ° C, the pressure on the high pressure gauge side is less than 9 kg / cm2, and the pressure on the low pressure side is Negative pressure), and there is frost or dew on the filter and capillary tube.
2. The cause of the failure: the dust in the refrigeration system adheres or adheres to the filter screen at the inlet end of the filter, or the interface between the capillary and the filter screen, so that a local throttling phenomenon is formed at this location, and the temperature drops rapidly, and condensation or condensation occurs Frost.
3. Treatment method: If there is frosting at the filter inlet, and the sound of intermittent airflow is heard, tap the filter body with a small wrench, the airflow sound changes, and the frost layer of the filter and capillary melts at the same time, which can be judged The filter inlet filter is clogged.
Op dit moment: ① Verwijder het capillair, maak het filter schoon, blaas het droog en installeer het opnieuw. Of vervang het filter ② evacueer en vul het koelmiddel tot de aangegeven hoeveelheid.